TCHP 17

This versatile unit, capable of delivering 19 kW, and can serve as a heat pump, a reversible heat pump, a chiller, or even a domestic hot water heat pump. Its unique design allows for simultaneous heating and cooling if you utilize both sides.

Get in touch

Flexible heat recovery from multiple sources

Cooling, heating, and domestic hot water simultaneously

Supply temperatures up to 90°C

Preconfigured

10" touchscreen user-friendly interface

Remote access and monitoring with 5G and Ethernet

Specifications

Refrigerant

CO₂

Compressor

Bitzer 4PTE-7K

Capacity control

CRII: 15-100%

Chilled water

+10°C til -10°C

Hot water

+30°C - +90°C

Inlet temperature up to

50°C

Heating 30/50°C (4/0°C 20% eth gly.)

19kW

COP Heating

3,3 - 5,42

Cooling 12/7°C (35/45°C)

16kW

COP Cooling

3 - 4,57

COP Domestic hot water (return cold side 10°C)

4,32

COP during heat recovery

7,2 - 8,7

Domestic hot water per minute (65°C)

5,0 l/min

Fuse size

40A

Voltage

400V

Dimensions

1462x690x1913mm

Water connection dimensions

28mm

Capacities and dimensions

Refrigerant

CO₂

Compressor

Bitzer 4PTE-7K

Capacity control

CRII: 15-100%

Chilled water

+10°C til -10°C

Hot water

+30°C - +90°C

Inlet temperature up to

50°C

Heating 30/50°C (4/0°C 20% eth gly.)

19kW

COP Heating

3,3 - 5,42

Cooling 12/7°C (35/45°C)

16kW

COP Cooling

3 - 4,57

COP Domestic hot water (return cold side 10°C)

4,32

COP during heat recovery

7,2 - 8,7

Domestic hot water per minute (65°C)

5,0 l/min

Fuse size

40A

Voltage

400V

Dimensions

1462x690x1913mm

Water connection dimensions

28mm

5.0
COP Heat
4.4
COP Cool
90°C
Water Temp
1
GWP

On average, this heat pump saves approximately

4
t
CO2e

(

4

metric tons CO2 equivalents each year) pr heat pump

Tequs Offshore

Tequs Offshore

Tequs Offshore is custom-designed CO2 machines ideally suited for offshore applications.

Tequs Offshore
Consulting

Project development and commissioning consulting

We at Tequs have a competent team and resources with extensive experience in the development of projects within refrigeration.

Project development and commissioning consulting
Commissioning

Pre-configuration and Startup packages

Are you aiming to reduce installation time? We can do the start up in our laboratory or out on site. If you need assistance with the startup or want us to pre-configure the unit, we can help you with this.

Pre-configuration and Startup packages
Hydronic kits

Tequs Flow

The entire water side in a box. We offer both standardized hydromodules and customized modules. It enables return temperatures up to 60°C. It allows for the provision of heating and cooling at multiple temperature levels simultaneously. 

Tequs Flow
Tequs Offshore

Tequs Offshore

Tequs Offshore is custom-designed CO2 machines ideally suited for offshore applications.

Consulting

Project development and commissioning consulting

We at Tequs have a competent team and resources with extensive experience in the development of projects within refrigeration.

Commissioning

Pre-configuration and Startup packages

Are you aiming to reduce installation time? We can do the start up in our laboratory or out on site. If you need assistance with the startup or want us to pre-configure the unit, we can help you with this.

Hydronic kits

Tequs Flow

The entire water side in a box. We offer both standardized hydromodules and customized modules. It enables return temperatures up to 60°C. It allows for the provision of heating and cooling at multiple temperature levels simultaneously. 

FAQ

What is a CO₂ Heat Pump?

Doesn't CO₂ contribute to global warming?

Are CO₂ heat pumps better than other heat pumps?

What are the applications of Tequs heat pumps?

Isn't it very demanding to install CO₂ heat pumps?

Aren't CO₂ heat pumps less efficient at high return temperatures?

How can you handle return temperatures as high as 50°C?

Contact us for more information

Thank you! Your submission has been received!
Oops! Something went wrong while submitting the form.